Home >> Product >> Rubber Cable |
|
|
Coil End Lead to BS6195 Type 4 |
|
|
Applications |
|
|
This range of Cables is designed as power leads for permanent connecton to coil winding motors, panel wiring and electrical machinery . They are able to withstand high temperature and immersion in varnish. Other applications include vehicle wiring. T he HOFR sheath resists oil and varnish and the stranding is designed as a compromise between flexibility and positional stability. Also suitable as an alternative to tri-rated and bi-rated cable in certain applications. |
Standards |
|
Cable in accordance with BS6195 ; Insulation & Sheath to BS6899 |
Construction |
|
Conductor: Flexible Tinned Copper to BS6360. |
|
Insulation: Ethylene Propylene Rubber E.P.R ; Type FR1 (Voltage Categories A & C) & Type FR2 (Voltage Categories D & E) to BS 7655. |
|
Sheath: Chlorosulphonated Polyethylene C.S.P. HOFR Black. To BS 6899. |
Technical Data |
|
Voltage Categories: |
|
|
|
A |
300/500V |
C |
600/1000V |
D |
1900/3300V |
E |
3800/6600V |
F |
6350/11000V |
|
|
Operating Temperature Range: |
-20°C to +70°C |
Bending Radius: |
Up to 25mm2 = 6 x overall diameter |
Above 25mm2 = 8 x overall diameter |
|
Sheath Colour |
|
|
0.5-10mm2: |
Red-Black |
|
10mm2 above: |
Black only. |
|
|
Options |
|
Coiled end lead is also manufactured to BS6899 Type 5 - Silicon insulation 180oC Operating Temperature. |
|
Voltage Category |
Maximum Equipment Test Voltage (ACrms) |
Nominal Voltage Rating of Cable Uo/U |
A |
2.5 |
300/500V |
C |
4.0 |
600/1000V |
D |
9.5 |
1900/3300V |
E |
17 |
3800/6600V |
|
|
|
|
Core and Size
mm2 |
Stranding (Number of
Strand/Strand Diameter) |
Nominal Thickness of Insulation mm |
Nominal Overall Diameter mm for each voltage category |
Voltage Category |
Voltage Category |
A |
C |
D |
E |
A |
C |
D |
E |
Mm |
mm |
|
|
|
|
|
|
|
|
0.5 |
16/0.2 |
0.8 |
1.4 |
- |
- |
3.3 |
4.5 |
- |
- |
0.75 |
24/0.2 |
0.8 |
1.4 |
- |
- |
3.5 |
4.7 |
- |
- |
1.0 |
32/0.2 |
0.8 |
1.4 |
- |
- |
3.7 |
4.9 |
- |
- |
1.5 |
30/0.25 |
0.8 |
1.4 |
- |
- |
4.0 |
5.2 |
- |
- |
2.5 |
50/0.25 |
0.9 |
1.4 |
2.8 |
- |
4.6 |
5.6 |
8.5 |
- |
4.0 |
56/0.3 |
1.0 |
1.4 |
2.8 |
- |
5.4 |
6.3 |
9.1 |
- |
6.0 |
84/0.3 |
1.0 |
1.5 |
2.8 |
- |
6.5 |
7.5 |
10.3 |
- |
10 |
80/0.4 |
1.2 |
1.5 |
2.8 |
- |
7.9 |
8.5 |
11.3 |
- |
16 |
126/0.4 |
- |
1.5 |
2.8 |
5.0 |
- |
9.6 |
12.4 |
17.2 |
25 |
196/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
11.4 |
13.8 |
18.6 |
35 |
276/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
12.8 |
12.5 |
20.0 |
50 |
396/0.4 |
- |
1.7 |
2.8 |
5.0 |
- |
14.8 |
17.1 |
22.1 |
70 |
360/0.5 |
- |
1.8 |
2.8 |
5.0 |
- |
17.2 |
19.2 |
24.2 |
95 |
475/0.5 |
- |
2.0 |
3.0 |
5.0 |
- |
19.2 |
22.0 |
26.3 |
120 |
608/0.5 |
- |
2.2 |
3.0 |
5.0 |
- |
21.9 |
23.5 |
27.8 |
150 |
756/0.5 |
- |
2.3 |
3.0 |
5.0 |
- |
24.1 |
25.5 |
29.8 |
185 |
925/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
26.3 |
27.5 |
32.1 |
240 |
1221/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
28.3 |
30.6 |
35.1 |
300 |
1525/0.5 |
- |
2.6 |
3.0 |
- |
- |
33.0 |
33.8 |
- |
400 |
2013/0.5 |
- |
2.8 |
3.0 |
- |
- |
37.4 |
37.8 |
- |
630 |
2106/0.6 |
- |
- |
3.2 |
- |
- |
- |
43.5 |
- |
|
|
Correction Factors |
|
For ambient air temperatures other than 40°C, the following factors should be applied: |
|
Ambient Air Temp |
Correction Factor |
1.140 |
1.100 |
1.050 |
1.000 |
0.945 |
0.900 |
0.835 |
0.775 |
0.705 |
0.603 |
0.545 |
0.445 |
|
|
Where cables are to be grouped in free air, the following factors should be applied: |
|
No. of Cables in Group |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Correction Factor |
0.80 |
0.70 |
0.70 |
0.60 |
0.56 |
0.50 |
0.50 |
|
|
Ambient air temperature 40°C
Conductor operating temperature 90°C |
Electrical Characteristics |
|
Resistance Values (ohms per kilometre) |
|
Nominal Conductor Area |
Nominal Conductor Stranding |
Max. DC Resistance at 20°C |
Max. Continuous Current Ratings
(BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |
|
|
|
|
Nominal Conductor Area |
Nominal Conductor Stranding |
Max. DC Resistance at 20°C |
Max. Continuous Current Ratings
(BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |
|